Brand Name: MGREENBELT
Model Number: MG-15CL
Place of Origin: Shandong, China (Mainland)
Air Cooled Glycol Water Chiller for Wort and Fermenters
1. Deatils of glycol water chiller for wort and fermenters
2.Technical specification of glycol water chiller for wort and fermenters
Model |
Unit |
MG-15CL |
Nominal cooling capacity |
kcal/h |
28855 |
KW |
33.5 |
|
Input power |
KW |
15.8 |
Power supply |
3PH-380V-50HZ, ohers available |
|
Refrigerant |
Type |
R22/407c |
Type of control |
Thermostatic expansion valve |
|
Compressor |
Type |
Hermetic scroll |
Power(kw) |
15HP |
|
Condenser |
Type |
Finned copper tube with axial fan |
Evaporator |
Type |
Tank with coil/shell and tube |
Chilled fluid flow(m3/h) |
4.87 |
|
Volume(L) |
270 |
|
Inlet and outlet pipe diameter(mm) |
DN40 |
|
Pump |
Power(kw) |
1.5 |
Lift(m) |
20 |
|
Dimension |
LxWxH(mm) |
1800*1000*1600 |
Weight |
kg |
750 |
Safety protection |
compressor over temperature,over current,high and low pressure,Phase sequence,phase-missing |
|
More glycol water chiller models for wort and fermenters
Optionas:
1) Power supply :single/3 phase, 208-240v, 380v-415v,440v-480v, 50hz/60hz
2) Available refrigerant: R22, R407C, R404A
3) Compressor: Panasonic, Copeland, or Danfoss
4) Supply -10c, -5c,0c outlet cold water
4.Glycol water chiller working drawing for wort and fermenters
This chiller is mainly for the indsutry that need below zero,so the glycol added to protect the evaporator from anti-freeze,normally used in the industry below:
*Wineries,Brewery,
*Food and Beverage processing
*Chemical processing
*Other cooling water low temperature industry
6.The low temperature water chiller was packed in the strong plywood case,no fumigation,if any other package needed,pls kindly tell us.
PACKING: Wooden case
SHIPPING: By sea or by air
7.Factory Introduction:
Q1: How to choose the right chiller?
A1:
1).Power supply voltage : PH/ V/ HZ?
2).Refrigerant type R22(Freon ) or CFC free one R407C?
3).What is the cooling capacity requests , KW?
4). What is the outlet water temperature and return water temperature to chiller?
5). Do you have the requests for the water flow rate , water pressure and water quality?
6). For what kind of equipment or cooling system( Close loop or open loop ) in your side?
7). What is the maximum ambient working temperature in your factory?
Q2: What power supply chiller you can produce?
A2: Our standard power supply is 3phase-380V-50Hz, Customzied different for optaions, like 3phase- 415V,440V,460V,480V,- 50Hz or 60Hz
Q3:What is your Payment terms?
Q3:Standard is 50% in advance to production, the balance before shippment, this mainly depends on the order.
Q4:What refrigerant you can supply?
A4: We have R22, Eeo friendly R407c, R410a, R134a,R404a depends on your choice.
Q5: What is your payment Terms?
1). 30%T/T in advance, 70% should be paid before shippment is our regular payment terms.
2). D/P, L/C is also acceptable for discussion.
3). Per your secial requests are also welcome for communicating
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes:Please contact with us ahead!!!
1.Our standard voltage supply is 380V/3P/50HZ.Different countries has different standards.It could be customized.
2.Refrigerant available:R22,R407C,R404A etc.
3.Various compressor brand.
4.Prices could be changed by products specification.But we will offer you the best price if you contact with us.
Libra Zhang
M: 008618769762328
Whatsapp/Viber : +8618769762328
E: chillercompressor at gmail dot com
Skype: libra5813
QQ: 2053526507